Why I have a popup error message “The simulator does not answer” when I start Simulator SoMachineBasic ?

SomachineBasic Simulator uses port 502 and this port may be used by any other Software ( Ex: Twidosuite, Unity simulators ...)

To check if the port 502 is really already reserved by another application Software,  execute in a DOS session the command "netstat- anbp tcp" ( see the result in attached copy screen)  

and then close/delete such application using this port 502 before starting the SomachineBasic Simulator 




 