Power Monitoring Expert - I have an ION 7650 meter with the v410 framework and cannot use this meter in the EN50160:2010 report

 When I try to run the EN50160:2010 report and include an ION 7650 meter with the v410 framework I see a message saying:

Source <my meter name> does not support the EN50160:2010 Standard. Remove it from the report and run again.

This is happening because the CFG_ItemValue table in ION_Network does not include this new framework in the list of frameworks that support the EN50160 report.

To correct this, run the following SQL statement to update CFG_ItemValue:

USE ION_Network

EXEC spCFG_SaveItemValueByName 'EN50160_V2010_Frameworks',

 '8000_FAC-PQ_V1.1.0.0.0·8000_FAC_V1.1.0.0.0·8650A_FAC_V4.2.0.0.1·8650B_FAC_V4.2.0.0.1·8000_FAC_PQ_V1.1.0·7400_FAC-PQ_V1.1.0·9410_SEA-PQ_V1.1.0·7650_FAC-PQ_V4.1.0.0.0·7650_FAC-PQ_V4.1.0.0.1·9610_SEA-PQ_V4.1.0.0.0'

 