Browse FAQs

How do you set up the reference template on the ATV320 drive for pedestal mode?

Published date: 15 October 2019

Issue:
Setting up the reference template on the ATV320 drive for pedestal mode?

Product Line:
ATV32 and ATV320

Environment:
All 

Cause:
Wants to have his  4 to 20mA reference signal follow 0 to 60hz even with a low speed setting on the drive of 10hz. 

Resolution:
Programming 
I/O Menu 
BSP= Reference template enter
Change to bLS= Pedestal mode.
Done

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.