Video: How to change type terminal control from sink to source or from source to sink on ATV61/71 drives?

Published date: 14 January 2019

Issue:
Configuring Sink Mode on Altivar 61 & 71 Drives

Product Line:
Altivar 61
Altivar 71

Environment:
All

Cause:
Terminal control mode configuration

Resolution:
First to get access to the control terminals open the cover on the control front panel.
Undo the locking screw until the spring is full extended.
Remote the card by sliding it downwards.
Now you will have access to the SW1 switch which has sink/source options.  
Move the dip switch accordingly.
Reseat the card back into its slot and re-tighten the locking screw to lock position.

 