ATV312 drive: Why is the preset speeds not overriding the analog signal when the hand off auto control is in auto mode?

Published date: 11 January 2019

Issue:
Why is the preset speeds not overriding the analog signal when the hand off auto control is in auto mode?

Product Line:
ATV312

Environment:
All 

Cause:
Fr2 does not support the preset speed override only Fr1

Resolution:
Using Fr1 and Fr2 for auto manual the preset speeds will only override the analog signal coming in on Fr1 not Fr2 this is normal behavior. 