How Unity Pro application can be restored from SD memory card to a CPU?

A Unity Pro application can be restored from SD memory card to Modicon PLC CPU like M580 and M340. 

1- Switch off the PLC
2- Insert the SDCard "where the application saved in" into the CPU
3- Switch on the PLC
Let the PLC for few moments till the application is being transferred to the CPU.