How can I determine what the PM5500 Front panel Status code means?

Issue
The meter's front panel status code is displayed in hexadecimal without a full explanation of what the hexadecimal value represents. The customer would like an explanation as to what this status means.

Product Line
PM5500 series (PM5560, PM5563)

Environment
Front panel

Resolution
Use the following instructions to decipher the status code. In this example, the status reads "0021 hex".
  1. Convert the hexadecimal value to binary.
0021 = 0000 0010 0001
Hex   Decimal
  1. Determine which Bits are a "1" or high.
0 0 0 0 0 1 0 0 0 0 1
Bit 11-16 Bit 10 Bit 09 Bit 08 Bit 07 Bit 06 Bit 05 Bit 04 Bit 03 Bit 02 Bit 01

In this example, Bit 01 and Bit 06 are high.
  1. ​Apply the Bitmap found in the Modbus Register List at Register 20003.
Bit 01 = Summary   ( on if any other bit is on - Maintenance Icon shown on HMI )
Bit 02 = RAM Failure
Bit 03 = NVRAM Failure
Bit 04 = RTC Failure
Bit 05 = Calibration Failure
Bit 06 = Clipping Detected
Bit 07 = Over-Running Energy Pulse Output
Bit 08 = Inp Mtr Diag Rate Exceeded/Backup RAM failure
Bit 09 = Lang File Mis Match
Bit 10 = Lang String Mis Match
Bit 11-16 Not Used 

Therefore, this device appears to be having a clipping issue, and the customer must evaluate the voltage and current inputs to confirm they are within the meter's specification.