ATV660 will not follow the speed signal in auto mode.

Published date: 17 April 2019

Issue:
ATV660 will not follow the speed signal in auto mode.

Product Line:
ATV660

Environment:
All 

Cause:
Reference 1 not assigned to the correct input. 

Resolution:

Checked programming we had to set it up for Auto manual control. 
Complete Settings 
Command and References menu 
REf 1 channel set to AI1
Profile - CHCF is Not Separate
REf 1 switching is DI3
REf 1 channel is AI2

 