EGX300: Network Time synchronization unsuccessful using NTP server

The EGX300 network time synchronization fails when attempting to use an NTP server.

Product Line
PowerLogic EGX300 Gateway

EGX300 Gateway

Improper configuration of the EGX300 gateway results in unsuccessful time synchronization attempts.


1. Ensure the default gateway is defined correctly if the NTP server is not located on the same Ethernet network segment as the EGX300. The default gateway may be configured from the Setup -> Ethernet & TCP/IP.

2. Configure the NTP settings via the Setup -> Date & Time. Ensure that "Enable Network Time Synchronization" is checked and that an primary NTP server IP address is defined correctly.

If using an internal NTP server on the network, verify the server list by following the steps below:

  1. Click on the Windows button
  2. In the "Search programs and files" box, type cmd and press Enter.
  3. If necessary, select cmd from the list of search results.
  4. In the command prompt window, enter w32tm /query /peers
  5. Check that an entry is shown for each of the servers listed above.