M580 CPU SMTP capability

Published date: 25 September 2018

Title
M580 CPU SMTP capability
 
Issue
M580  CPU SMTP capability
 
Product Line
M580
 
Environment
Unity Pro
 
Cause
N/A
 
Resolution
 The M580 CPU does not have SMTP capability. Therefore, there is no Send_Email functionality like the M340 CPU . 

The M580 CPUs do support the MBP_MSTR and L9_MSTR block. However, for the MBP_MSTR function block, the M580 CPUs only support the following operation codes: 1 = Write data, 2 = Read data, 14 = CIP Explicit Message, 15 = Send Modbus Request, 23 = Read / Write data. 

The SMTP protocol is included in CTRL NOC (BMENOC0321). From the user manual, based on predefined events or conditions, messages are created using the DATA_EXCH function block. 
This will be the SMTP solution available for M580.
 