Pm800 analyzer shows negative value of kvar.I changed the direction of the current transformer and this time the kw value is negative read. How should we solve it.

1. Check the system setup to be correct as per Table 6 or 7 depending of the network type where PM800 is wired to measure.
Check the wiring to be according to System type setup and diagram type as per page 5.
Installation Guide is here:
ID => 2242629
Title => PowerLogic Series 800 Power Meter Installation Guide
URL => http://download.schneider-electric.com/files?p_Doc_Ref=63230-500-282

2. Find out which is the polarized terminal of the Current transformers. 
Negative kW is because current transformers connection are not correct polarized. 
As normal the polarized secondary CT should come to terminals I12, I14, I16.
Attached is a document "PM800 Instrument Transformer Wiring Troubleshooting" extrass from User Manual. Please check the CT wiring based on this document.

3. If nothing is help, please send to Technical Support following information:
3.1. If meter is connected to a communication network, use ION Setup last version and collect the information as per attached document "PM meters informtaion request".
3.2 If there is not possible to use ION Setup, use meter Display settings and take the pictures that contain the information settings as per attached documents "PM800 Settings check" and "PM800 Diagnostic".

Additional information here:
ID => 671738382
Title => PowerLogic Series 800 Power Meter PM810, PM820, PM850 & PM 870 User Guide
URL => http://download.schneider-electric.com/files?p_Doc_Ref=63230-500-225A2
ID => FA212816
Title => Where can I download the latest version of ION Setup software?
URL => http://www2.schneider-electric.com/support//en/faqs/content/?country=APS&lang=en&locale=en_US&id=FA212816
ID=> 19617256
Title => PowerLogic™ ION™ Setup 3.0 User guide
URL => http://download.schneider-electric.com/files?p_Doc_Ref=7EN02-0312-00
ID => 7385716351
Title => PowerLogic ION Setup 3.0 Device Configuration Guide
URL => http://download.schneider-electric.com/files?p_Doc_Ref=7EN02-0293
Was this helpful?
What can we do to improve the information ?