Why would the ATV71 drive show auto turning pending?

Published date: 03 September 2019

Issue:
ATV71 drive shows auto tuning pending.

Product Line:
ATV61 and ATV71

Environment:
All 

Cause:
The drive will not pass auto tune if the power removal input PWR is open

Resolution:
Status is PRA. Found jumper +24-PWR loose. Tightened and the auto tune  is now completed.