What's the Behavior of the Redundant Power Supply Modules BMXCPS4002 in case of pressing the Reset Button of the Active Power Supply?

The Behavior will not be changed, Active and Slave power supply Modules will be at their original status, Active Power Supply will not switch to slave because the power is still present on the backplane when pressing Reset Button
The only way to switch from Active Power supply to Slave one is when switching off the feeding power to the Active Power Supply 

 