How can you connect the VW3A3616 Ethernet card to the ATV320 C suffix or compact version drive?

Issue:
How can you connect the VW3A3616 Ethernet card to the ATV320 C suffix or compact version drive?

Product Line:
ATV320 with C suffix only 

Environment:
All 

Cause:
There is not a slot for the Ethernet card card to fit the ATV320 with C suffix. 

Resolution:
The VW3A3616 card will not fit directly into the ATV320........ C  or compact version drive without the VW3A3600 add on option. 
The VW3A3616  card will fit directly into the ATV320 ....... B or Book self version without the need of the VW3A3600 add on option. 

 