Technical FAQs

Ask a Question

M580/M340 BMXNOR0200 Unsolicited behavior


Title
M580/M340 BMXNOR0200  Unsolicited  behavior
 
Issue
M580/M340 BMXNOR0200  Unsolicited  behavior
 
Product Line
M340 M580
 
Environment
Unity Pro
 
Cause
N/A
 
Resolution
Engineering stated that, If an Unsolicited Trigger occurs in Class 1, or any Unsolicited enabled Class, that the BMXNOR0200 module will transmit all events from all classes that have Unsolicited Enabled.

 
Was this helpful?
What can we do to improve the information ?