Video: How to configure a Vista grouping object to open the correct meter diagram?

Issue
Customer would like configure a Vista grouping object to open the correct meter diagram.

Product Line
ION Enterprise 5.6, 6.x
Struxureware Power Monitoring 7.x
Power Monitoring Expert 8.x

Environment
Vista

Resolution

  1. Right-click on the grouping object to open the Grouping Object Configuration window
  2. Specify Node
    • Select the Node tab
  • Select Custom and navigate to the desired meter.
  1. (Optional) Specify the grouping object image
    • In the Display tab, select Custom
    • Select the desired image. Images of native devices are located in \Power Monitoring Expert\config\diagrams\images\default
  1. Specify the Action
    • In the Action tab, select Open Diagram for Meter Template
  1. Press OK
  2. Press Save to save the changes
  3. Double-click on the grouping object to verify the grouping object functions properly