Issue:
Can you use multi-motors on ATV320 drives?
Product Line:
ATV320
Environment:
Multi-motors
Cause:
n/a
Resolution:
Yes, but need to size the drive according to the sum of the max current of all the motors and provide overload protection for each motor.
You also need to turn off Output Phase Loss on the drive [DRI- > CONF -> FULL -> FLT].