How to NTP time sync M580 PLC through BMENOC0311 module ?

***** With the release of Unity Pro v13.0 HF2 and BMENOC03x1.4 firmware 2.12 this can be accomplished using the "Update CPU time with the module:" setting in the NOC. ******

For versions previous to the above, find here attached project backup as a ready solution to time synch M580 CPU through NOC module over NTP.

Note :-
- You need to enable block and pulse time sync variable to sync PLC clock. Refer settings done here.
- Enable NTP time service in DTM browser of NOC module and provide NTP time server IP address.