ATV212HD15N4 mounting info needed on spacing mounting vertically.

Published date: 28 June 2019

Issue:
What is the minimum mounting space between the top and bottom of the ATV212H series drives?

Product Line:
Altivar ATV212 drive

Environment:
All 

Cause:
Wants to mount the ATV212 Drives vertically.

Resolution:
The ATV212 installation manual has the Drive mounting generalities. 
In this case the min mounting clearance between the top and bottom of the drive is 2 inches top and 2 inches from the bottom. 

The ATV212 Drives side to side mounting is also 2 inches if the top cover is still in place on the drive.  If you remove the top cove you can mount side by side no minimum distance. 


 