How Much Data is in the Power Monitoring Expert Database for a Particular Meter?

Issue:
Database growth can become problematic when gone unchecked. Knowing how much data a meter has in the Power Monitoring Expert database can be useful in determining which sources need to have their logging parameters examined and possibly adjusted. 

Product Line:
StruxureWare Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x, 8.x

Environment:
SQL Server Management Studio
ION_Data Database

Resolution:

*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

The attached MeterRowDataCount.sql will return a list of all sources in the ION_Data database, as well as the rowcount and data size information for that meter in the DataLog2, EventLog2 and WaveformLog2 tables. 



Note: This query may take several minutes to run. Database size and server hardware specs will cause the run times to vary. A 400GB database containing over 5.3 billion rows of information in the DataLog2 table was used for testing, and the run time was approx. 12 minutes. 