Search FAQs
How do I troubleshoot an Altivar Process Drive that would not connect or communicate to a DeviceNet device or network?
Issue:
Altivar Process Drive that will not connect or communicate with a DeviceNet device or network.
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Note: This FAQ goes over some basic checks and troubleshooting tips. For extended troubleshooting please refer to your drives DeviceNet manual.
Drive Will Not Connect
Altivar Process Drive that will not connect or communicate with a DeviceNet device or network.
Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
Environment:
All serial numbers for Altivar Process Drive
Cause:
N/A
Resolution:
Note: This FAQ goes over some basic checks and troubleshooting tips. For extended troubleshooting please refer to your drives DeviceNet manual.
Drive Will Not Connect
- Communication Module
- DeviceNet is not integrated on the Altivar Process drives. Must use module VW3A3609.
- The VW3A3609 Fieldbus module, with a minimum V1.6IE01 firmware version, is compliant with the Altivar process product range.
- Only one communication module can be used at a time
- Installation
- Module must be inserted in Slot A ONLY at the bottom of the control part.
- Pin Layout - Make use to use proper pinouts
- Isolate any electrical interference
- Use conduits
- Separate control and power connections
- Add terminating resistors if the drive is at the end or the last of device in the network.
- Network
- Check for any duplicate addresses on the network.
- Check to make sure you have proper configured assemblies
- Programming
- Check Basic Settings on the drive. Make sure the following is set:
- IP Address
- Baud Rate
- Data rate used
- Make sure drive is power cycled after any Communication settings are changed.
- Check for properly configures assemblies
- Check Basic Settings on the drive. Make sure the following is set:
- Troubleshooting
- Check LEDs on the drive
- See Fieldbus Status LEDs, LED MS Network Status and LED MS Module Status attachments
- Drive Connects But Will Not Run
- Check LEDs on the drive
- Network
- Verify you can read from the drive
- Verify reading and write to correct Modbus registers
- Programming on the Drive
- Confirm drive is setup for Network Control
- Check Command and Reference Menu
- [Complete settings] [Command and Reference]
- Check Command and Reference Menu
- Confirm drive is setup for Network Control
- Troubleshooting
- Check Communication Map
- [Display] [Communication map]
- Check Command Channel
- Command Register
- Ref Freq Channel
- Ref Freq
- [Display] [Communication map]
- Check Communication Map
Released for:Schneider Electric Global
Attachment(s)
Explore more
Explore more