Why do we say you can have longer motor leads using non-shielded cable than shielded cable from a drive?

Published date: 26 July 2019

Issue:
Is shielded or non-shielded cable recommended for longer motor leads?

Product Line:   
Altivar drives
 
Environment:  
All
 
Cause:  
N/A
 
Resolution:  
 A shielded cable will have more stray capacitance to ground as compared to a non-shielded cable.  
So the longer the shielded cable the more leakage current that can occur to ground.
This leakage current can cause nuisance ground detection faults.
 