How to reset peak demand from the front display of a CM4000

Product Line
CM4000 series

Keys on the front display.


To reset the demand peak values, follow the procedure below:

  1. From the Front Panel Main Menu, select Resets
  2. Select Demand. The password prompt displays.
  3. Select your password. The default password is 0.
  4. The Reset Demand Screen displays. Select the value that you need to reset. Available options are Peak Power Demand and Peak AMP Demand.
  5. Press Enter on the selected option. The No option starts to blink
  6. Use the Up arrow to change to Yes, then press Enter. The Yes will stopp blinking
  7. Press the Menu button. You will get a confirmation that the Reset was complete. 
  8. Press the Menu button two more times to return to the Main Menu Screen.