ATV320 Why can't I assign the logic inputs in the I/O menu?

Published date: 07 March 2019

Issue:
  ATV320 Unable to change the logic inputs in the I/O menu.
 
Product Line: 
 ATV320
 
Environment:
 All
 
Cause:
  Programming logic inputs
 
Resolution:  
You can not assign a function to the logic inputs in I/O menu.
Those are  read only parameters.  
You must assign a logic input to the function you need.  
Example, If you want to assign freewheel stop to LI2, you would need to go to CONF / FULL / FUN / STT, then go to NST and assign LI2 to NST.