Can you branch out from a variable to multiple function block input in Unity Pro?

Issue:
Can you branch out from a variable to multiple function block input in Unity Pro?

Product Line:


Environment:


Cause:


Resolution:
Unity Pro does not allow branching out from a variable to multiple function block input pins.  A viable work around would be to use the MOVE block and the output of the MOVE can be branched out to the inputs of the function blocks.