Is there a RS-485 cable to connect a M221 to a Magelis XBTN401?

No. There is no cable you have to make your own the pin out is as follows;

4--------4
5--------5
7--------7
8--------8

No other pins can be used because the M221 can also be configured for RS-232. (can not use a straight through Ethernet cable).