Technical FAQs

Ask a Question

Free xml weather feed for US airports

Issue
User would like to import weater feed data from local airport for free

Product
ION Enterprise 6.x
StruxureWare Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x, 8.x

Enviornment
Designer with VIP XML import module

Resolution

1) Navigate to http://w1.weather.gov/xml/current_obs/ and using the navigation option to determine the station ID for the desired airport.
ex CYYJ is Victoria International Airport

2) Open Designer and login with user that has permissions to edit nodes.

3) Open desired VIP with tool box open

4) Drag and drop a new XML Import module. Right click to edit the properties

5) Under the URL Setup register add the URL of the specific location desired.
ex http://w1.weather.gov/xml/current_obs/CYYJ.xml

6) Under xPath Query 1, add the desired parameters
ex /current_observation/temp_f

7) Modify the label of the output register to match the name or the desired measurement
ex Temp_f

Was this helpful?
What can we do to improve the information ?