What is the duration of the in-rush current of an HMISTU855 at startup?

Published date: 09 January 2019

Issue: The user manual of the HMISTU855 does not specify the duration of the in-rush current of an HMISTU855 at startup.

Product Line: HMISTU, HMIS5T

Resolution: The duration of in-rush current during the startup of an HMISTU855 has been tested to be no more than 2.5ms. The in-rush current during startup has been tested to be no more than 30 Amps.