What should the F601 current limit parameter be set to in the ATV212 drives?

Published date: 09 October 2018

Issue:
What should the F601 current limit parameter be set to in the ATV212 drives?

Product Line:
ATV212

Environment:
All

Cause:
What should the F601 current limit parameter be set to in the ATV212 drives?

Resolution:
The F601 Current limit parameter should be set to 110% of the Drives current rating. 
Note: If you use a small size motor on a larger drive, you will need to adjust this setting to the motor FLA times 1.1.