How do you set up the ATV312 for auto manual control?

Published date: 03 October 2018

Issue:
How do you set up the ATV312 for auto manual control?

Product Line:
ATV312

Environment:
All 

Cause:
Want to set up an 3 position switch for HOA control. 

Resolution:

CTL menu 
Fr1 = Ai1
Fr2 = AI3
RFC = LI3

You will need to also turn off preset speeds:
FUN menu
PSS
PS4 set to no