How to upload or download files on ATV630/ATV930 drives using VW3A1111.

Published date: 22 March 2019

Issue:
How to open/save and transfer file on the VW3A1111 remote keypad for the Altivar Process Drive?

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
N/A

Resolution:
Save to HMI (Keypad)

From the main menu, Go to [File management] [Transfer config file] [Copy from the Drive]

Transfer Back to the Drive From HMI
From the main menu, Go to [File management] [Transfer config file] [Copy to the Drive]

PC
Plug HMI to PC with mini USB connector and open HMI folder and go to (DRVCONF) folder and open .cfg file