Technical FAQs

Ask a Question

Why are we seeing SW Time loss (Breaker Comms Comms Module) lost and Restored Events in Web Apps even if it is disabled under Events/micrologic.evt?

Title:
Why are we seeing SW Time loss (Breaker Comms Comms Module) lost and Restored Events in Web Apps even if is disabled under Events/micrologic.evt?

Issue:
SW Time loss (Breaker Comms Comms Module) lost and Restored are showing up under Event under Web Applications even after the event has been disabled under
Schneider Electric\Power Monitoring Expert\System\Translators\Events\micrologic.evt.


Product Line:
Power Monitoring Expert 8.1
Web Applications

Evironment:
PME Web Applications

Cause:
PME 8.1 is report false events for the micrologic trip units (SW Time Loss Breaker Comms Module Lost and Restored)

Resolution:
This issue has been reported as a bug in PME 8.1  and it will be fix in PME 8.2
The workaround for PME 8.1 is to apply a hotfix fix to allow the Micrologic nuisance events to be suppressed
 It is replacing the attached dll file from the Schneider Electric\Power Monitoring Expert\System\Bin  Directory.

To deploy:
1. Shut down the siteserv service and close the web applications on the server
2. Rename the existing file in the \system\bin directory - xlMicrologic.dll
3. Swap in the attached file
4. Restart the siteserv service
5. Start the Web Applications and check the Events.


 