Issue
Customer need to know how to make a database archive manually

Product Line
Power Monitoring Expert (PME) 8.x
StruxureWare Power Monitoring (SPM) 7.x

Environment
Database archiving 

Cause
Need to make a full archive, or an archive of a certain period of time of the live database without modifying it.

Resolution

To make an archive of the database please follow the video and instructions below.

Note: Make sure that the user you are logging in with have SQL Sysadmin rights. Otherwise you will get an error "Computername\useraccount cannot open the Database Manager. To open the Database Manager a user must be a member of the SQL Sysadmin server role". 
User has to be either added to the Sysadmin account or have the credentials to a Sysadmin account to follow the steps below.



Archive databases are attached to the system. Please detached it before making a copy, or moving it to a different location.

1. Open Database Manager
2. Click on Tools> Database Manager
3. If the error "Computername\useraccount cannot open the Database Manager. To open the Database Manager a user must be a member of the SQL Sysadmin server role" pop up. click ok If the error doesn't pop up go to step 7
4. Navigate to the DatabaseManager.exe location. Usually located at install drive:\\Program Files (x64)>Schneider Electric>System>bin> DatabaseManager
5. Press and hold Shift and Right click on it. Then select Run as different user.
6. Enter username and password of the SQL Sysadmin user and press ok
7. Once the Database Manage pops up make sure that the database is the correct database.
8. Click on "..." to navigate to the location where the archive is going to be saved. Click save
9. Select the date range, or the beginning of the database and the end date that is desired for this archive.
10. Make sure that the "Remove Archive data from the live database" check box is not checked.
11. Click on Ok, and the system would show a message when it finished the archive.
12. Navigate to the location where the archive was saved to make sure the file was added to the correct location.