What is the standard overload range for form H30 on an 8536 type S starter?

Published date: 21 May 2019

Issue:
SSOLR code for 8536 type S Starter

Product Line: 
NEMA Type S starters

Environment:
Type S Full Voltage Contactors and Starters

Resolutions
The standard overload range will depend on the starter size.  Note the range can be changed.  Check the Digest for details on modifying the form. 
 
Size 00 0 1 2 3 4 5 6 7
(SSOLR comes standard)
Amp Range 3-9 6-18 9-27 15-45 30-90 45-135 90-270 180-540 270-810