What is the TTL for a Quantum 140NOC78x00?

 
Goals and Symptoms

What is the TTL (Time To Live) for a Quantum 140NOC78x00?

 
Facts and Changes
 
The TTL (Time To Live) for a Quantum 140NOC78x00 is 1 for firmware versions less than 1.70 for Point to Point EIP communications through routers. 

The TTL is 64 for firmware versions equal to or greater than 1.70 for Point to Point EIP communications through routers.
 
The TTL remains at 1 for Multicast EIP communications.


Causes and Fixes

If a TTL greater than 1 is required for Point to Point EIP communications, then upgrade the 140NOC78x00 firmware to version 1.70 or higher.

Firmware v1.70 was released in March of 2016.
 
 
 