What does Obr mean on Drive Status display when ramping down on ATV61 and ATV71?

Published date: 04 February 2019

Issue:
Has Obr on Drive Status display when ramping down on ATV61 and ATV71

Product Line:
ATV61, ATV71, Altivar 61, Altivar 71

Environment:
All

Cause:
N/A

Resolution:
Obr is a drive state and not a fault. It is displayed in the top left corner of the graphic keypad if the drive is decelerating and using the Auto-Adapted Deceleration Ramp to avoid a possible overbraking fault (ObF). This status may show up when Decel Ramp Adapt parameter is enabled.