Technical FAQs

Ask a Question

Error A320 on a LXM32 drive

Issue:
What is error A320 on a LXM32 drive?

Product Line:
Lexium 32

Resolution:
A320 is a following error. The parameter is _SigLatched Bit 8
Reason could be a high external load or an acceleration that is too high.
Solution is to reduce external load or acceleration or use a differently rated drive.
Error response can be adjusted via parameter ErrorResp_p_dif
Was this helpful?
What can we do to improve the information ?