What would cause the ATV212 drive to ramp up to 30hz then display retry and start up all over again?

Published date: 14 March 2019

Issue:
What would cause the ATV212 drive to ramp up to 30hz then display retries and starts up all over again?

Product Line:
Altivar ATV212 and ATV21

Environment:
All

Cause:
Drive is resetting on phase loss or fault, and is trying to restart.

Resolution:
1st check to see if the auto reset is set in parameter F303.  If its on try turning it off to see if the drive will give you a fault on the retry.
2nd check to see if the input voltage on the Drive is balanced phase to phase and to phase to ground. 
 