What is the voltage supply to the ATS48 fan kits?

Published date: 04 June 2019

Issue:
Customer wants to troubleshoot the ATS48 fan not running.

Product line:
ATS48, Altistart 48

Environment:
all

Cause:
OHF - Overheating

Resolution:
The cooling fans are supplied with 12Vdc.  The voltage tolerance on the fans is 6-13Vdc, 315mA.  You can test operation of the fans with something such as a 9V battery, if a 12Vdc source is not available.  This should provide enough power to move the fans.  

 