Can you connect DC voltage supply to the DC bus on the ATV6xx/ATV9xx Process drives?

Issue:
Can you connect DC voltage supply to the DC bus on the ATV6xx/ATV9xx Process drives?

Product Line:
ATV600 / ATV900 Process drives

Environment:
All models, All serial numbers

Cause:
Information not available in current literature.

Resolution:
Yes, it is possible to connect the proper DC voltage directly to the DC bus of the ATV9xx Process drives with a precharge circuit.  However, the ATV6xx Process drives cannot take a direct DC connection. 