Browse FAQs

How to enter Pump Curve Data on an Altivar 6xx Process Drive?

Published date: 25 July 2019

Issue:
How to enter Pump Curve Data on an Altivar 6xx Process Drive?

Product Line:
ATV6xx

Environment:
All models and serial numbers

Cause:
To monitor behavior of pump curve

Resolution:
ATV630 Process Drive Pump Curve Setup
 
Prerequisites to entering Pump Curve Data 
Initial Configuration
  • Motor Settings
  • Speed Control Settings
Pump Curves
  • Enter pump characteristics & activate pump curves

Initial Configuration

 
Complete Settings => Motor Parameters + AutoTune (Also available in Simply Start Menu)
Base Frequency (BFR)  = 60 Hz
Motor Power (NPR) =
Nominal Motor Speed (NSP) =
Nominal Motor Current (NCR) =
Motor Thermal Current (ITH) =
Motor Control Type (CTT) =
Auto Tune (TUN) =
 
Complete Settings => Macro Config
Application Selection (APPT) = General Pump Control
 
Complete Settings => Define System Units
P Sensor Unit (SUPR) = ft
Flow Rate Unit (SUFR ) = GPM
Temperature Unit (SUTP) = F
 
Simply Start
Low Speed LSP =
High Speed HSP =
Acceleration ACC =
Deceleration DEC =

Pump Curves

Pump Characteristics curves entered
Activate Curves
 
 

Pump Characteristics (Data Sheet)

 

 
Point Flow
(GPM)
Head
(Ft)
 
Head
(psi)
Power
(HP)
1 0 80.9   76.8
2 2585 59.5   71
3 4509 49.5   70.2
4 6737.7 27.1   61
5 7720 16   51.8
BEP 5560 40.1   66.8
 
The following pump curve settings can be made through the Keypad display, SoMove configuration software or the embedded web page.
Complete Settings => Pump Characteristics
Pump Curve Mode (PCM) = PHQ
Pump Speed (PCSP) = 1190
Flow 1 (PCQ1) = 0
Flow 2 (PCQ2) = 2585
Flow 3 (PCQ3) = 4509
Flow 4 (PCQ4)  = 6737.7
Flow 5 (PCQ5) = 7720
Flow BEP (PCBQ) = 5560
Head 1 (PCH1) = 80.9
Head 2 (PCH2) = 59.5
Head 3 (PCH3) = 49.5
Head 4 (PCH4) = 27.1
Head 5 (PCH5) = 16
Head BEP (PCBH) = 40.1
Power 1 (PCP1 = 76.8
Power 2 (PCP2) = 71
Power 3 (PCP3) = 70.2
Power 4 (PCP4) = 61
Power 5 (PCP5) = 51.8
Power BEP (PCBP) = 66.8
Pump Curve Activate (PCA) = YES

Was this helpful?

What can we do to improve the information ?

Can't find what you are looking for?

Reach out to our customer care team to receive information on technical support, assistance for complaints and more.