How to control a Vijeo Designer HMI panel navigation using a SoMachine PLC

Issue:
Control a Vijeo Designer HMI panel navigation using a SoMachine PLC

Product Line:
Vijeo Designer, SoMachine

Resolution:
You start by creating a SoMachine variable of type INT and share it with Vijeo Designer through the Symbol Configuration.
Once this is done, you should link this variable to an internal variable in Vijeo Designer called _CurPanelID.
Writing 1 in this variable will make the HMI display panel # 1 (See attached).