Osisense XU - How to make a deviation of 90° beam in an XU thru-beam photoelectric sensor.

A customer did a deviation of 90° beam with an XUK2LA* thru-beam by using an XUZC* standard reflector. Unfortunately it does not operate properly.
Q) How to make such beam deviation correctly?
A) You need a use a mirror device for such application. A reflector cannot deviate the beam. See attached drawing. Such mirror accessory exists in our Preventa XUSL light curtains offer.