Can radio buttons spawn multiple panels in Vijeo Designer?

Published date: 24 July 2019

Issue:
Looking for a way to use a group of radio buttons on several panels in Vijeo Designer. The radio buttons need to remember their last state after a panel change.

Product Line:
Vijeo Designer

Resolution:
By design, the radio buttons do not spawn multiple panels in Vijeo Designer. After a panel change, the states are reset.

To have the desired behavior, you need to implement it. You will need to make use of Switch with Lamp objects and global actions. The Switches will set the respective bits. The Global actions need to be setup in order to reset any group of bits whenever a corresponding bit is set. The switches will take the state of the bit and will show the correct status after a panel change.


 