How to use Quantum analog modules and EFBs on M580 ERIO?

Goals and Symptoms

How can we configure the EFBs O_SET and O_SCALE to properly work on the 8 channels of an analog card 140ACI3000 located in a remote Quantum drop in a M580 configuration ?
Facts and Changes
M580, Quantum CRA
Causes and Fixes
In the setup, you will need the 140CRA31200 and the analog module, in this case the 140ACI03000
In the FBD section, there is no need to use the QUANTUM EFB.
Just use the DROP EFB and let the pin SLOT unconnected

Then you can use the same EFBs than on Quantum (ACI030, I_SCALE, ...)