How is a dynamic braking resistor added to an ATV32 drive?

Published date: 24 September 2018

Issue:
How is a dynamic braking resistor added to an ATV32 drive?

Product Line:
Altivar 32

Environment:
All

Cause:
N/A

Resolution:

Wiring:
The resistor should be wired to the PA and PB terminals on the drive.

Programming:
DRI- > CONF > FULL > FUN- > STT
Go into CONF menu, then FULL menu, then FUN menu.
Under FUN, go into STT- menu.
Set brA to [No].

For more details see the ATV32 Programming Manual:
http://ddc-prd.schneider-electric.com:9080/en/download/document/S1A28692/