Video: Why won't the ATV630 drive run in reverse?

Published date: 10 May 2019

Issue:
ATV630 won't operate in reverse.

Product line:
ATV600, ATV630, ATV650, Altivar Process

Environment:
All

Cause:
Configuring Reverse Motor Operation on Altivar 630 Process Drives

Resolution:
The Factory settings for the Process Drive to run in reverse is disabled in Reverse Disable parameter. 
Go to Complete Settings > Command and Reference > Reverse Disable, change the setting to No and save.  Now, you should be able to operate the drive in Reverse.

 