What is the rise time (slew rate) of the PWM output signal of an ATV312 series drive?

Published date: 10 May 2019

Issue:
What is the rise time (slew rate) of the PWM output signal of an ATV312 series drive?

Product Line:
ATV312 series drives.

Environment:
All models, All serial numbers, Any switching frequency rate

Cause:
Customer has a motor that requires a DV/DT filter if the rise time is less than 2 microseconds but this information is not available in current literature.

Resolution:
The Rise time of the 3 phase PWM output of the ATV312 series is 0.1 microseconds.  This is not significantly affected by changes in switching frequency.