What is error t1CF on the Altivar Process 900?

Published date: 27 March 2019

Issue:
What is Thermal Sensor Error (t1CF) on the Altivar Process 900?

Product Line:
Variable Frequency Drives

Environment:
Applies to Altivar Process 900
ATV930
ATV940
ATV960

Cause:
Drive displaying "t1CF" when wiring the sensor to "AI1" and "COM"

Resolution:

t1CF: AI1 thermal sensor Error

Probable Cause:
The thermal sensor monitoring function has detected a thermal sensor error on analog input AI1:
  • Open circuit, or
  • Short circuit

Remedy: Verify the sensor and its wiring, replace the sensor if needed

This detected error can be cleared with [Auto Fault Reset] Atr or manually with the [Fault Reset Assign] rSF parameter after the cause has disappeared.

 