Does setting the RPM value matter in ATV71/ATV61 drive or is it used just for displaying motor speed?

Issue:
Does setting the RPM value matter in the ATV71/ATV61 drive or is it used just for displaying motor speed?

Product Line:
ATV61 ,ATV71

Environment:
All

Cause:
N/A

Resolution:
Entering Motor RPM or the Nominal Motor Speed does matter. It provides information about the motor characteristics to the drive. how much slip it has at Full Load.

 